Diesel Genset (community-scale backup)

EDT domain: d01_renewable_energy_storage

Definition

A community-scale backup diesel generator (genset) — the firming backstop that covers the windless / sunless stretches a solar+wind+battery system cannot economically span. It is dispatchable and the standard off-grid resilience option, but its fuel is bought-in (an import), so every backup kWh is expensive and emitting. In the NI engine it is the default D20 backstop technology. CR_030

Role — backstop, not baseload

  • Reaching 100% reliability from renewables alone requires uneconomic oversizing, so an off-grid community either carries a genset backstop or designs to <100% reliability. CR_030
  • It runs only during deficits, so capex is low but per-kWh cost is high — the opposite profile to PV/wind. OT_063

Cost & performance

  • Genset capital cost is low — ~USD 300–800/kW installed — but LCOE is the highest of all off-grid options, ~35–120 ¢/kWh, because fuel dominates. OT_063
  • Fuel: NZ diesel ~NZD 3.0–3.5/L (2026). Mature, dispatchable, covers durations from hours to seasonal. CR_030

Fuel store — the D34 seven-day autonomy tank

D34 sizes a 7-day fuel store (autonomy_total_days). The engine costs it at diesel_tank_capex_per_l = 4 NZD/L — a value tagged assumed (dq low), bracketed by but not established by the only verified NZ retail anchors, the Promax list prices captured 2026-07-14. URL_022

ProductCapacityPrice (incl GST)$/LDiesel-rated?
Bunded Diesel Tank500 L$3,805$7.61Yes (“Diesel Grade UV stabilised LDPE”)
Bunded Oil Collection Tank1,000 L$2,913$2.91No — waste-oil collection
Bunded Oil Collection Tank2,000 L$4,079$2.04No — waste-oil collection

URL_022

$4/L bridges two unevidenced gaps at once

The only diesel-rated price is **7.61/L** (500 L). The cheap /L figures come from waste-oil tanks used as a shell proxy — not diesel-rated. So 4 NZD/L assumes both a scale economy (half the small diesel tank’s per-litre) and a spec premium (double the oil-spec shell). No NZ vendor publishes a diesel-rated price in the 1–2 kL band; Sebco and Fuelchief are quote-only. Supply-only — excludes install, base, pipework, and any recurring compliance cost. A written vendor quote for a diesel-rated 1–2 kL self-bunded tank is still an open gap. URL_022

Where the fuel store goes — and what the law actually requires (REG_016)

A building is permitted but NOT required. reg 17.63 is precisely the genset tank (“supplies the internal combustion engine… directly through pipework” with a class 3.1D substance), and 17.63(2) caps a tank inside a building at 25,000 L (non-fire-resistant) / 50,000 L (fire-resistant) — orders of magnitude above a community store. So an above-ground outdoor bunded tank is the simplest compliant form. REG_016

Siting choiceConsequence
Above ground, outdoorsNo compliance certificate below 5,000 L (reg 17.90(2)(a)(iv); diesel = class 3.1D). Separation distances apply above 500 L.
Below groundCompliance certificate required at ANY size (reg 17.90(2)(a)(i)). Do not bury the tank.
Inside a buildingPermitted; the 25,000 / 50,000 L caps are far above a community store.

🔴 The "recurring compliance certificate" was WRONG

An earlier reading held that “diesel ≥500 L on a stationary engine → WorkSafe stationary-container compliance certificate (recurring, fee unquantified)”, and it was carried as an OpEx risk. It is false. The 500 L figure appears twice and neither is a certificate trigger for diesel: reg 11.4(2)(c)‘s 500 L is a separation-distance threshold, and reg 17.90(2)(a)(ii)‘s 500 L is for gas. A 1–2 kL above-ground diesel tank needs no certificate and carries no recurring fee. REG_016

Three constraints that DO survive:

  1. Separation distances above 500 L of diesel (reg 11.9 → Schedule 12 Table 5, class 3.1D column). Extracted 2026-07-15: an above-ground diesel tank sits back from a dwelling (protected place) by 1.5 m at 1,000 L / 2 m at 2,500 L / 3 m at 5,000 L, and 0 m from a public place up to 2,500 L. So a 1–2 kL store needs a ~1.5–2 m ring from dwellings — smaller than the Sch 1A 2 m inter-dwelling spacing, so rarely binding, but now a sourced number for the site-layout model. REG_016
  2. Bunding — HSW does not require it below 10,000 L for class 3.1D (Table 9). ⚠ But a spill reaching water is an RMA s15 discharge (REG_012), regional plans commonly require it, and the URL_022 tanks are self-bunded anyway → model it bunded.
  3. “In a workplace” — Part 17 applies only to a stationary container system “in a workplace” (reg 17.1(1)). Whether a purely residential community counts as one is unsettled, and it gates whether the regime applies at all.

The renewable-diesel (HVO) and biodiesel fuel options

  • HVO renewable diesel is a drop-in (EN15940) — same genset, no engine change — cutting lifecycle CO₂ ~70–90% at a ~10–30% fuel premium. But it is not yet available at NZ pumps (import/fleet only; government removing barriers). CR_030
  • B100 biodiesel (FAME) is a fuel variant for the same genset (with cold-flow and storage caveats), but NZ supply is fragile — Z Energy closed its Wiri plant by 2022, and the cost is ~1.5–1.8× fossil diesel — so it is a niche, not a reliable backstop fuel. CR_030

NZ off-grid cases

  • Chatham Islands / Point Durham: 3× Vestas V27 + 576 kWh battery + diesel backstop, 62–68% renewable; diesel spend fell from 1.8M to ~600k/yr, avoiding ~1,300 t CO₂/yr against a historic ~129.5 c/kWh cost. URL_012
  • Stewart Island/Rakiura optimisation designs a 100%-renewable multi-carrier microgrid to displace diesel entirely — achievable but capital-heavy. LIT_033
  • Where a grid exists, grid connection is itself the preferred “backup” — isolated networks are the most vulnerable. Interview II [INT_002]

Relevance to Neobiome (D20)

The model’s default backstop technology. Its fuel is a bought-fuel import that reduces SSI (extends D18) — the same import-flow mechanism as bought biomass wood (biomass_district_heating), so the engine models both with one concept. Sizing is set by the reliability target: design to 100% with a genset (import) or to an accepted LPSP ~1–5% unmet and shrink/remove it. HVO and biodiesel are fuel-variant swaps that keep the genset but lower its carbon. CR_030

Open questions

  • Community-scale genset capex (NZD/kW) and standby fuel-burn for a representative remote NZ install — would firm the backstop cost cell.
  • NZ HVO retail/bulk price (NZD/L) once the fuel reaches market.